Overview of ZQDF solenoid valve: The ZQDF solenoid valve is an actuator used in an industrial process automation control system. It can automatically open or close the valve after receiving an electronic control signal to realize the on-off or flow adjustment control of the fluid medium in the pipeline, thereby controlling the temperature and flow rate in the system. , Pressure and other parameters are automatically adjusted or remotely controlled.

  • Item NO.:

    XUVAL77-87
  • Lead Time:

    45Days
  • Product Orgin:

    CHINA
  • Brand:

    XUVAL
  • Shipping Port:

    Shanghai
  • Payment:

    100%TT
  • Color:

    Silvery
  • MOQ:

    10
Products Details

ZQDF steam solenoid valve

ZQDF solenoid valve series solenoid valve products can be widely used in production and scientific research departments such as textiles, printing and dyeing, chemicals, plastics, rubber, pharmaceuticals, food, building materials, machinery, electrical appliances, and surface treatment, as well as in people's daily life facilities such as bathrooms, canteens, and air conditioners. . ZQDF solenoid valve series are mainly used for the control of air, steam, coal gas and other gaseous media; ZQDF-Y series are mainly used for tap water, distilled water, frozen brine, electroplating waste liquid and other liquid media, and also used for oil with viscosity less than 4°E kind.



ZQDF solenoid valve product features:
1.Corrosion resistance: The main components, valve plugs and valve bodies are made of stainless steel and cast steel, with good corrosion resistance.
2.Heat resistance: Electromagnetic and sealing parts are all made of special high temperature resistant electrical materials and sealing materials, and effective heat insulation measures are adopted.
3.Wear resistance: reasonable selection of materials, clever use of fluid lubrication between the valve plug and the valve body to reduce wear.
4.Condensation resistance: The cold north water of the steam pipe is an important factor that affects the action of the steam solenoid valve, and this valve is not affected by condensate water.


Structure and principle of ZQDF solenoid valve:

The ZQDF solenoid valve is a step-by-step direct pilot solenoid valve, which can be divided into a normally closed solenoid valve and a normally open solenoid valve according to the difference between the on and off states when the power is off. Normally closed solenoid valve. After the coil is energized, the armature first drives the valve plug of the auxiliary valve to lift under the electromagnetic force. The fluid on the main valve cup flows away through the auxiliary valve, reducing the pressure acting on the main valve cup. When the pressure on the valve cup is reduced to a certain value, the armature drives the main valve cup and uses the pressure difference to open the main valve cup and the medium circulates. After the coil is de-energized, the electromagnetic force disappears, and the armature is reset due to its own weight. At the same time, depending on the medium pressure, the main and auxiliary valves can be closed tightly. Normally open solenoid valve. After the coil is energized, the moving iron core moves down due to the suction force. The valve plug of the auxiliary valve is pressed down, the auxiliary valve is closed, and the pressure in the main valve cup rises. When the pressure rises to a certain value, the main valve cup The upper and lower pressure difference is the same. Due to the electromagnetic force, the moving iron core loses under the main valve cup, and the main valve seat is compressed and the valve is closed. When the coil is de-energized, the electromagnetic suction force is zero, the auxiliary valve plug and the supporting iron core are lifted up due to the action of the spring, the auxiliary valve opens, and the fluid on the main valve cup flows away through the auxiliary valve, reducing the effect on the main valve cup When the pressure on the main valve cup is reduced to a certain value, the main valve cup is pushed up by the pressure difference, the main valve opens, and the medium flows.


Main technical parameters of ZQDF steam solenoid valve:

Model
ZQDF-1 ZQDF-2 ZQDF-3 ZQDF-1Y ZQDF-2Y ZQDF-3Y
Nominal pressure MPa
1.6
Working pressure difference MPa
DN15~50
0~1.6
DN65~100
0.05~1.6
Type of medium
Gas, air, etc.
Saturated Vapor
Superheated steam or high temperature gas
Water, oil and liquid
Hot water, oil
Oil
Medium temperature ℃
≤60 ≤180 ≤220 ≤60 ≤180 ≤220
Voltage
Other specifications of AC220V can be made for special order
Service life
According to JB/T7352-94
Leakage m1/min
According to JB/T7352-94
Power consumption
AC≤70VA DC≤60W
Explosion-proof mark
dIIBT4
Explosion-proof certificate number
CE991010
Outlet connector
Internal thread M20×1.5
Ambient temperature
-40~+60℃


ZQDF steam solenoid valve outline dimension and connection form table:

Nominal diameter
DN
Dimensions
internal thread
Dimensions
Flange connection
H L G H L D D1 D2 b f N-d
15 148 92 1/2 176 130 95 65 46 14 2 4-14
20 148 92 3/4 181 150 105 75 56 16 2 4-14
25 148 110 1 210 160 115 85 65 16 3 4-14
32 182 120 11/4 221 180 140 100 76 18 3 4-18
40 182 140 11/2 230 200 150 110 84 18 3 4-18
50 192 162 2 252 230 165 125 99 20 3 4-18
65 - - - 265 290 185 145 118 20 3 4-18
80 - - - 276 310 200 160 132 20 3 8-18
100 - - - 373 350 220 180 156 22 3 8-18


ZQDF steam solenoid valve installation instructions:
1. When installing the ZQDF solenoid valve, the solenoid valve coil should be upward and keep the vertical position. The arrow or mark on the solenoid valve should be consistent with the flow direction of the pipeline, and it should not be installed in a place with splashing or water leakage.
2. The working medium of the solenoid valve should be clean and free of particulate impurities. The dirt and filter on the surface of the solenoid valve internals should be cleaned regularly.
3. When the solenoid valve fails, in order to isolate the solenoid valve in time and ensure the normal operation of the system, it is best to install a bypass device .
4. In the pipeline system, the diameter of the solenoid valve installed on the branch should be smaller than that of the main pipeline valve.
5. Before installing the solenoid valve, the pipeline must be cleaned. It is recommended to install a filter in front of the valve and install a trap in the steam pipeline.
6. The valve cannot be installed in the low recess of the pipeline, so as not to prevent the action due to the precipitation of steam, condensate, impurities, etc. in the valve.
7. The ordinary type cannot be used in explosive hazardous situations.
8. When the rigidity of the pipeline is insufficient, it is recommended to fix the pipeline in front of the valve with a bracket to avoid vibration when the solenoid valve is working.
9. Before installation, pay attention to read the product label, carefully read the instruction manual, and judge whether the product meets the conditions of use.
10. Pressure gauges should be installed on the pipes before and after the solenoid valve to observe the pipe pressure.


ZQDF solenoid valve use and maintenance:
1. It is recommended that the user unit send a special person to be responsible for use and maintenance.
2. After the solenoid valve is installed, it needs to pass in the medium for several experiments, and it can be put into formal use after confirming that it is normal.
3. The dirt on the inside and outside of the large valve and the suction surface should be cleaned regularly, and be careful not to damage the sealing surface.
4. When the solenoid valve is not used for a long time, the manual valve in front of the valve should be closed. When it is reactivated, the steam solenoid valve should drain the condensed water and make a trial operation several times. It can be put into use after the switch is normal.
5. When the solenoid valve is removed from the pipeline and not in use, the internal parts should be wiped clean and blown with compressed air for storage.
6. When using for a long time, if the seal between the piston and the valve seat is not good, the sealing surface of the piston can be ground again, and then ground with the valve seat.
7. When working, pay attention to the pressure gauges before and after the valve. The working pressure must not exceed the rated pressure, and the working pressure difference must be within the range of the rated pressure difference. When the working pressure exceeds the rated pressure or the working pressure difference exceeds the rated pressure difference, the solenoid valve should be stopped and the front and rear manual valves should be closed to prevent the solenoid valve from exploding and leaking.


Product Structure:




Packing & Delivery : 

Packing Details:all by seaworthy plywood case and packed strongly by packing belt as below
Delivery Details:Generally it is 5-10 days if the goods are in stock. or15-30 days if the goods are OEM or not
enough subject to the order quantity. But anyway, normally, we are able to make sure the delivery will not exceed 45days.







Send A Message

If you are interested in our valves and want to know more details,please leave a message here,we will reply you as soon as we can.

  • #
  • #
  • #
  • If you have questions or suggestions,please leave us a message,we will reply you as soon as we can!

Related Products
Remote control float valve
Cast iron remote control float valve 100X

Competitive Advantage: 1. 18 Months Guarantee for quality. 2.OEM manufacturer, print client’s LOGO on the valve body. 3.Offer Operation Manual & Install Introduction for safety use. 4.Offer manufacturer’s reasonable price to win the market for both. 5.Accept any the third party inspection. 6.As a factory, every production process can be controlled during manufacture. 7.Offer inspection & testing reports for raw materials, production process, wall thickness, face to face dimension, pressure test, welding test, painting test, etc.

Pressure reducing valve
200X Pressure reducing valve

200X pressure reducing valve is a kind of valve used for parallel connection of fire water and domestic water in the water supply system, used to allocate the direction of water supply.

Slow closing check valve
Stainless steel 300X Slow close check valve

Check valve can regulate the opening and closing speed. When the pump starts or stops running, it can be adjusted to the best opening or closing speed with the on-site adjustment.It is suitable for mining enterprises and high-rise buildings to reduce water hammer and water hammer in direct water supply and drainage system by water pump, so as to achieve the effect of safe closing.

500X pressure relieving/sustaining valve
Stainless steel 500X pressure relief valve

The 500X relief/hold valve is mainly used in fire fighting or other water supply systems to prevent system overpressure or to maintain pressure in fire fighting water supply systems.

400X Flow control valve
Cast iron 400X Flow control valve

400X flow control valve is a kind of valve used to allocate the direction of water supply in parallel water supply system for fire protection and domestic use.

600X hydraulic electric valve
Cast iron 600X hydraulic electric control valve

The 600X electric control valve is a hydraulic operated valve with solenoid valve as the guide valve.

700X Pump control valve
700X Water pump control vavle

700X water pump control valve is a kind of reverse valve installed at the outlet of water pump in high-rise buildings and other water supply systems to prevent the backflow of media.

Brass pressure reducing valve
Brass flange pressure reducing valve

Flange pressure reducing valve from the general thread of the pressure reducing valve, its connection flange, this is a control valve in the body of the opening of the opening and closing of regulating the flow of medium, the medium pressure is reduced, at the same time with the aid of the role of the valve after pressure adjust the opening of open-close part, keep the valve after pressure within a certain range, under the condition of the inlet pressure changing, keep the outlet pressure within the scope of the set, protection appliances for production from then on.

200P Pressure reducing valve
Brass 200P pressure reducing valve

Model 200P pressure reducing valve is a direct acting type adjustable pressure reducing valve, using diaphragm type hydraulic operation, can be installed horizontally or vertically in water supply, fire fighting system or other clean water system.

Copyright © 2024 Tonglu Yongxin Valve Co.,Ltd.All Rights Reserved. Powered by dyyseo.com

IPv6 network supported

IPv6 network supported

top

Send A Message

Send A Message

    If you are interested in our valves and want to know more details,please leave a message here,we will reply you as soon as we can.